Wire Gauge Calculator

Determine the correct wire gauge based on current, distance, and voltage drop requirements

Circuit Parameters

Maximum continuous current draw

Wire Run

Panel to load (not round-trip)

Additional Settings

How Wire Gauge Is Determined

Choosing the right wire gauge involves two separate checks: ampacity (can the wire safely carry the current without overheating?) and voltage drop (will too much voltage be lost over the wire length?). The required wire gauge is the larger of the two results.

Voltage Drop Formula (Single Phase):

Vdrop = (2 × L × I × R) ÷ 1000

Where L = one-way distance (ft), I = current (amps), R = resistance (ohms per 1,000 ft)

Voltage Drop % = (Vdrop ÷ Source Voltage) × 100

NEC Ampacity Table (NEC 310.16)

AWG Diameter (in) Copper Ampacity Aluminum Ampacity Common Use
60°C 75°C 60°C 75°C
14 0.064" 15A 15A — — 15A lighting circuits
12 0.081" 20A 20A 15A 15A 20A outlets (most common)
10 0.102" 30A 30A 25A 25A 30A dryer, water heater, AC
8 0.128" 40A 50A 30A 40A 40-50A range, EV charger
6 0.162" 55A 65A 40A 50A 50-60A sub-panels, large AC
4 0.204" 70A 85A 55A 65A 70-85A feeders
3 0.229" 85A 100A 65A 75A 100A sub-panel feeders
2 0.258" 95A 115A 75A 90A 100-115A feeders
1 0.289" 110A 130A 85A 100A Large feeders
1/0 0.325" 125A 150A 100A 120A 150A service entrance
2/0 0.365" 145A 175A 115A 135A 200A feeders (copper)
3/0 0.410" 165A 200A 130A 155A 200A service (copper)
4/0 0.460" 195A 230A 150A 180A 200A service (aluminum)

Based on NEC Table 310.16 for not more than 3 current-carrying conductors in raceway/cable at 30°C ambient temperature.

Copper vs. Aluminum Wire

Copper

  • • Better conductivity (lower resistance)
  • • Smaller wire size for same ampacity
  • • More durable and corrosion-resistant
  • • Required for most branch circuits
  • • More expensive per foot
  • • Standard for 14-10 AWG residential

Aluminum

  • • 61% the conductivity of copper
  • • Needs larger gauge for same ampacity
  • • Much lighter and less expensive
  • • Common for service entrance (SE) cable
  • • Requires anti-oxidant compound
  • • Must use AL-rated connectors and breakers

Wire Sizing Tips

  • Always size wire for the breaker, not just the load — a 20A breaker requires #12 AWG minimum
  • For continuous loads (running 3+ hours), multiply the current by 1.25 before sizing
  • Voltage drop becomes the controlling factor for long runs, even at low amperage
  • Low-voltage circuits (12V, 24V) need much heavier wire than 120V for the same wattage
  • Always check local codes — they may be stricter than the NEC minimum
  • Derate ampacity when more than 3 conductors are in a conduit or ambient temperature exceeds 30°C
  • Use stranded wire for conduit runs (easier to pull) and solid wire for NM-B (Romex) residential
  • Ground wire can be one size smaller than the circuit conductors per NEC 250.122

Important: This calculator provides guidance based on NEC standards. Actual wire sizing must account for ambient temperature, conduit fill, conductor bundling, and local code amendments. All electrical work should be performed by a licensed electrician and inspected per local requirements.

As an Amazon Associate, we earn from qualifying purchases.

Recommended Calculator

Casio FX-991ES Plus-2nd Edition Scientific Calculator

Casio FX-991ES Plus

The professional-grade scientific calculator with 417 functions, natural display, and solar power. Perfect for students and professionals.

View on Amazon